In the last issue we spoke
of contactor coil characteristics and how both high and low voltage
could cause coil burn-out. We also described how a typical three-phase
pump panel and a Franklin deluxe control box has both a main power
circuit and a separate control circuit.
In this issue we will discuss circumstances which
can result in contactor coil burn-out or the failure of the contactor
to dropout (shut off the motor) even though the control switch has
opened. The Figure to the right shows a contactor and control
circuit for a single-phase unit, although this condition could affect
either a single- or three-phase contactor. Note that in the example
there is more than 300 feet of wire between the contactor and the
control circuit switch. Again the control switch could be a pressure
switch, float switch, time clock, or other control device(s).
>There will always be some capacitance between the
two wires in the control circuit. With normal control circuit lengths,
this capacitance causes negligible voltage on the coil. However,
if the length of the wire is long enough, this voltage may exceed
the coil's sealing or must hold voltage
rating and keep the coil energized. The resultant coil voltage can
also be either high or low enough to cause coil burn-out (remember
the contactor characteristics' example from the last issue). If
the capacitance happens to be near a specific ratio to the coil's
inductance, a phenomenon called series resonance
can cause the coil volts, or cable volts, or both, to exceed the
line voltage. One test demonstrated that 0.8 microfarad open-switch
control cable capacitance created 420 volts across the coil-with
only 240 volts input! Specific tests conducted at Franklin Electric
have shown that cable capacitance of as little as 0.1 microfarad
could keep a contactor closed even though the control switch had
opened. Tests have also shown that as little as 0.2 microfarad could
cause contactor coil burn-out.
The length of control circuit wire necessary to
set up this type of capacitance will vary from a few hundred to
several thousand feet. Factors such as cable type, cable size, and
burial locations (wires side by side or separated) are some of the
factors contributing to this condition. In addition, different brands
and types of contactors are affected differently.
Also, keep in mind that these same symptoms may
be caused by wiring problems such as ground fault or shorts between
the wires. With all power removed and all control
switches opened, if there is any continuity between the two control
circuit wires, the wires are shorted or connected together somewhere.
Continuity is always checked with the POWER OFF and generally
an ohmmeter is used. Always carefully troubleshoot the control circuit
before assuming the coil problems are caused by control cable capacitance.
Shorted connections can also be caused by a malfunctioning switch
or timer. You should also eliminate possible damage caused by mice,
moles, fire-ants, or other insects.
|
| While there is no
known one size fits all method of curing conditions
of high control cable capacitance, it can usually be solved
by connecting either a resistor or capacitor across the contactor
coil. Franklin recommends that any time there is more than 300
feet of cable between the contactor and the control switch,
a capacitor should be added across the contactor coil (Figure
to the right). The capacitor should be a continuous duty,
AC capacitor, like the gray or silver run capacitors used in
Franklin's larger control boxes. Note: Run capacitors are
available in both plastic and metal cases. If metal cased capacitors
are used, they must be grounded. Recommended ratings are
shown in the Figure below. The contactor Franklin uses
typically has four (4) quick-connect terminals located on the
contactor's coil. Two are used to supply power to the coil and
two are not used. Connect the new run capacitor to the two empty
terminals. Connecting a run capacitor to the coil terminals
normally assures drop-out and safe coil voltages with all cable
lengths and contactor models. Note: this run capacitor is
an additional capacitor. You can not use an existing control
box run capacitor for both the motor power circuit and the control
circuit. Run capacitors are typically found inside Franklin's
1 ½ through 15 Hp single-phase control boxes. |
|
|
|